characteristic:
■ The microfiltration membrane module uses a PVDF reinforced membrane, which is resistant to fouling, easy to clean, and has a long service life.
■ The membrane modules are bundled and distributed, with reasonable spacing between membrane fibers, which can maintain filtration flux and reduce sludge clogging.
■ The membrane fibers at the bottom of the membrane module are encapsulated using proprietary technology, which avoids the problem of fiber breakage during the swinging process of the bottom membrane fibers.
■Suitable for the treatment of urban sewage, reclaimed water, industrial wastewater, landfill leachate, and other wastewater.

MBR membrane module technical parameters
Membrane module model | NL@F-1000M | NL@F-1500M | NL@F-2000M | NL@F-Z30M | ||||
Basic parameters | Membrane module height (mm) | 1025 | 1525 | 2025 | 2265 | |||
Membrane module length (mm) | 620 | 620 | 620 | 2025 | ||||
Effective membrane area (m2) | 10 | 15 | 20 | 30 | ||||
Membrane fiber material | PVDF | |||||||
Membrane fiber pore size (μm) | 0.1 | |||||||
Membrane fiber inner/outer diameter (mm) | 1.0/2.2 | |||||||
Water collection pipe materials | ABS | |||||||
Sealing materials | Epoxy resin | |||||||
Save method | Wet preservation / Dry preservation | |||||||
Running parameters | Design flux (L/(m2・h)) | 10~25 | ||||||
Operating mode | Suction filtration | |||||||
Suction pressure (kPa) | -5~-50 | |||||||
Stop-start ratio | 9min: 1min | |||||||
Backwashing method | Air-water backwash | |||||||
Backwash time (s) | 30 | |||||||
Backwash flow rate (m³/h/curtain) | 0.3 | 0.5 | 0.6 | 0.9 | ||||
Backwash pressure (MPa) | ≤0.1 | |||||||
Air scrubbing intensity (m³/h/curtain) | 3.0 | 4.5 | 6.0 | 8.5 | ||||
Maintenance cleaning method | Physicochemical cleaning | |||||||
Maintenance cleaning cycle (d) | 6~10 | |||||||
Maintenance cleaning agent, concentration | NaClO (200-500 mg/L) | |||||||
Chemical cleaning cycle (monthly) | 6~12 | |||||||
Chemical cleaning methods | Physicochemical cleaning | |||||||
Chemical cleaning agents, concentration | NaOH (0.02%) + NaClO (1000 mg/L) + Citric Acid (2%) | |||||||
Note: The above parameters are all reference values. The operating control parameters of the membrane module should be set reasonably according to the actual situation. | ||||||||